TM5-6130-301-13&P
(d) Remove attaching screw and nut from bus bar, jumper (8) and remove bus bar jumper.
(e) Remove circuit breaker power lead.
(f) Remove two phillips head screws that secure boot, circuit breaker (9), retainer plate, circuit
breaker, 20 amps (12) to panel.
(g) Remove circuit breaker (20 amp) by tilting upward.
(5) Receptacle assembly.
(a) Loosen panel fastener screw (1) and open panel (2).
(b) Remove screws securing receptacle assembly (13) to panel.
(c) Remove two screws that separate receptacle and remove upper half of receptacle.
(d) Loosen two screws from power leads of lower half of receptacle and remove.
NOTE
Remove attaching hardware from heat sink bridges and from the bus
bar ground, if applicable, to receptacle assembly being removed.
(6) Diode.
(a) Loosen panel fastener screws (1) and open panel.
(b) Remove receptacle power lead from diode (14).
7. Relay.
(a) Loosen panel fastener screws (1) and open panel.
(b) Remove receptacle power lead from relay, 200 Amps (15).
(c) Remove bus bar connectors (7).
(d) Remove wire lead from toggle switch (16) to relay 200 Amp.
(e) Remove mounting screw and hardware from relay and remove relay.
(8) Resistor.
(a) Loosen allen head screws on control knob (17) and remove knob.
(b) Loosen panel fastener screws (1) and open panel.
(c) Remove power leads from resistor, (18).
(d) Remove resistor mounting screws and remove resistor.
(9) Panel assembly distribution. Disassembly procedure for the Panel Assembly requires removal of
components attached to panel as listed in Chapter 5.
5-4