Table 4-1. Organization Troubleshooting (Continued)
PROBABLE CAUSE
CORRECTIVE ACTION
3. UNCONTROLLED STATION DOES NOT CHARGE BATTERY.
Circuit breaker faulty.
Replace circuit breaker.
Diode open.
Receptacle assembly faulty.
Step 1. Visually check for faulty contacts.
Replace receptacle assembly.
Replace receptacle assembly.
4. AMMETER READS HIGH OR ALL BATTERIES BOIL ON UNCONTROLLED STATION.
Input voltage too high.
If this occurs at all stations reduce input voltage.
5. CURRENT CONTROL FAILS TO CONTROL VOLTAGE.
Rheostat shorted.
Clean or replace rheostat.
6. POWER SWITCH WILL NOT CUT POWER.
Switch sticking closed.
Replace switch.